SD Standard Exhaust Fans

SKU#:

SD SERIES

8” & 10” Models

  • Smooth, quiet, reliable, maintenance-free operation
  • Durable steel construction with grey powder coat finish
  • 2 speed fan with high efficiency Euro design external rotor motor
    •  Totally enclosed with sealed ball bearings
    •  Pull chain speed control
    •  9 foot cord with 115 volt, 3-prong plug
  • Swept back, high efficiency, low noise blade design
  • Quiet, aluminum shutters with tie bar to maximize airflow and a magnet to prevent flapping and provide a superior seal
  • Zinc plated OSHA guard
  • Fans shipped completely assembled
  • Easy to install! Mount fan using four screws, plug it in and turn it on
  • Now upgraded with tie bar shutters and magnets for quieter operation and superior seal!

12” to 48” Models

  • Single, two and variable speed models are available.
  • All fans use a totally enclosed, thermally protected motor.
  • Rugged steel welded box housing has a durable powder coated finish.
  • Aluminum louver shutters are supported by long life nylon bushings  (30”, 36”, 42” & 48” have aluminum louvers).
  • 12” - 24” models have heavy wire chrome plated OSHA guards on intake side of fan.
  • 12" - 24" models now upgraded with tie bar shutters and magnets for quieter operation and superior seal!
  • 30”, 36”, 42” & 48” models have grey powder coated guards.
  • All fans are shipped completely assembled.

Canarm’s standard fans follow a tradition of quality in design, materials and construction.  All our standard fans are developed to be efficient and economically priced.  All variable speed standard fans use an energy efficient variable speed, dual voltage motor and blade combination.

To determine the proper Canarm Fan for your applications, use the following formula.

Number of cubic feet in room / Number of minutes per air change  = Required C.F.M. Capacity.

**Example**
A general office, (see chart) which requires an air change every ten minutes, would require the following fan capacity.    
If office is 100’ x 40’ x 10’ = 40,000 cubic feet.

 40,000 cubic feet / 10 minutes per air change  =  4000 Required C.F.M.

From this chart, you would select a fan that is rated at 4000 C.F.M. at  1/8” S.P. (Static Pressure).

FAN SELECTION CHART

MODELSPEEDBLADE
DIAMETER
RPMHPVOLTAGEAMPS
(FLA)
WEIGHT
(LBS)
dB(A)
@5 ft
CFM @ STATIC PRESSUREFRAMING
DIMENSIONS
0.000.100.1250.25
SD08Two81600/130025W1150.21348360/292270/150230/110--11 X 11
SD10Two101480/115060W1150.51555500/388420/300400/250--13 X 13
S12-E1Single1216251/41152.72863164015401510139015 X 15
S12-E2Two121725/11401/41153.432641650/10901550/9501520/9301390/015 X 15
S12-EVDVariable1216251/3115/2305.0/2.53260165015401510139015 X 15
S14-E1Single1416251/41152.73067217020702030186017 X 17
S14-E2Two141725/11401/41153.434652180/13502080/11902060/11601890/017 X 17
S16-E1Single1616251/41152.73368237022702210206019 X 19
S16-E2Two161725/11401/41153.436692380/16402280/14902230/14302070/019 X 19
S16-EVDVariable1616251/3115/2305.0/2.53663237022702210206319 X 19
S18-F1Single1816251/31154.13773320030903040292021 X 21
S18-F2Two181725/11401/31155.5/2.943743200/21003090/18903040/18202920/021 X 21
S18-FVDVariable1816251/3115/2303.8/1.94574315030502980286021 X 21
S20-F1Single2016251/31154.14177342032203170292023 X 23
S20-F2Two201725/11401/31155.5/2.945773440/23003240/20003180/19502930/023 X 23
SD24-F1Single2411001/31153.64670500045004300360027 X 27
SD24-GVDVariable2410751/3115/2304.4/2.25672505049104810440027 X 27
SD30-G1DSingle3010751/3115/2304.4/2.27282800070006000500033 X 33
SD36-G1DSingle368501/2115/2306.6/3.388721000085008000620039 X 39
SD42-H1DSingle428501230512283BHPFEIBHPFEIBHPFEIBHPFEI45 X 45
0.851.350.871.450.871.450.921.41
1286011580110909029
SD48-H1DSingle488501230514084BHPFEIBHPFEIBHPFEIBHPFEI51 X 51
0.821.560.841.670.841.690.831.48
1447012610122008400
RPM Minimum is determined when louvres are opened one inch. Some models are available with explosion proof motors. Please see SD-XPF.
Note: Wind has a significant effect on exhaust fans. A 10 mph wind creates a 0.05” pressure against the fan. A 20 mph wind creates 0.20” pressure and 30 mph a 0.45” pressure. These pressures are in addition to the static pressure in the building. Wind blocks or hoods should be included in all designs where fans will be subjected to winds above 10 mph.
CFM values listed are summarized for convenience. For full performance data refer to our Delair program.
Embedded image
     
SD08_SD10_DimsDwg.jpg   
8" & 10" MODELS   
FAN
SIZE
ABCD
(c/c)
E
SQR
N   
8"13 1/4"7 9/16"4"12"10 3/4"2   
10"15 1/4"7 7/8"4"14"12 3/4"3   
SD12_48_DimsDwg.jpg
  
12" to 48" MODELS   
FAN
SIZE
A X A
SQUARE
BCD
(c/c)
EN   
12"17 1/4"17"6"16"14 3/4"3   
14"19 1/4"17"6"18"16 3/4"3   
16"21 1/4"17"6"20"18 3/4"4   
18"23 1/4"18"6"22"20 3/4"4   
20"25 1/4"18"6 3/4"24"22 3/4"5   
24"29 1/4"18"6 3/4"28"26 3/4"5   
30"35 1/4"18"6"34"32 3/4"16   
36"41 1/4"18"6"40"38 3/4"20   
42"47 1/4"18"6 3/4"46"44 3/4"24   
48"53 1/4"19"6 3/4"52"50 5/8"26