Specifications

TYPICAL MAXIMUM CFM @ SP 
MODEL1/2” SP1” SP1 1/2” SP2" SP2 1/2" SPMin HPMax HP 
CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW)CFMBHPFEIFEPact (kW) 
20714000.680.800.6913000.690.960.7011000.661.050.6710000.721.080.738000.731.040.741/63/4 
20920000.750.910.7618000.751.090.7615000.711.210.7211000.711.120.728000.711.040.721/63/4 
920925001.360.651.3024001.410.811.3423001.50.911.4221001.481.011.4019001.491.071.411/61 1/2 
21030001.460.771.3828001.410.961.3426001.491.041.4123001.51.091.4219001.471.081.391/61 1/2 
921030001.460.711.3828001.410.901.3426001.491.001.4123001.481.071.4019001.461.071.381/61 1/2 
21237001.440.861.3733001.470.991.3929001.51.071.0324001.471.101.3916001.430.931.361/61 1/2 
921249002.910.632.62460030.742.7042002.920.842.6339002.990.912.6935002.920.982.631/63
21561002.90.772.6158002.950.932.6550002.980.962.6841002.930.942.6437002.931.002.641/33 
921577004.950.624.3372004.880.744.27680050.834.3763004.960.914.3458004.970.964.351/35 
21897004.930.744.3290004.970.864.3582004.950.964.3374004.971.014.3562004.940.984.321/25 
921895004.950.714.3388004.910.854.3080004.940.934.3272004.980.984.3661004.920.974.311/25 
92201600014.780.4512.501540014.880.5412.501480014.960.6212.601410014.90.6912.601330014.80.7512.503/415 
CFM values listed are summarized for convenience. For full performance data refer to our Delair program. 
Power rating (BHP) does not include transmission losses.  Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effect of appurtenances (accessories). 
For expanded FEI data click here. 