Specifications

MODELMOTORTYPICAL MAXIMUM CFM @ SP
HPVariable SpeedMax RPMSpeed1/4"1/2"3/4"1"1 1/4"
CFMBHPFEIFEPact (KW)CFMBHPFEIFEPact (KW)CFMBHPFEIFEPact (KW)CFMBHPFEIFEPact (KW)CFMBHPFEIFEPact (KW)
709DD050EC1/2Y*1200High1850---1650---1425---1250---500---
Low600---500---500---500---450---
709DD100EC1Y*1200High24000.990.840.8822750.990.930.8820870.970.980.8714000.591.160.554720.281.160.28
Low6000.062.000.095000.101.660.135000.161.420.185000.221.280.234000.261.130.27
710DD050EC1/2Y*1100High1900---1400---1050---750---500---
Low600---500---500---500---400---
710DD100EC1Y*1100High26000.970.830.8722500.980.830.8719000.990.800.8816000.770.990.707000.590.770.55
Low6000.101.440.095000.161.170.185000.260.950.275000.370.950.364000.441.130.27
712DD050EC1/2Y*1000High2650---2300---1900---1425---1100---
Low800---600---600---600---500---
712DD100EC1Y*1000High35751.001.090.8932500.981.170.8729500.981.220.8726750.991.250.8820000.801.300.72
Low8000.081.960.116000.111.700.136000.181.420.206000.251.270.266000.331.150.33
*Minimum motor speed 425 RPM (EC Models).
EC Motors can be controlled using the built in potentiometer on motor or by using a 0 to 10 V controller, or by a remote potentiometer.
REVIEW FAN CURVES BEFORE ADJUSTING RPM TO ENSURE LOAD DOES NOT EXCEED MOTOR HP.