Specifications
TYPICAL MAXIMUM CFM @ SP | ||||||||||||||||||||||
MODEL | 1/2” SP | 1” SP | 1 1/2” SP | 2 SP | 2 1/2 SP | Min HP | Max HP | |||||||||||||||
CFM | BHP | FEI | FEPact (kW) | CFM | BHP | FEI | FEPact (kW) | CFM | BHP | FEI | FEPact (kW) | CFM | BHP | FEI | FEPact (kW) | CFM | BHP | FEI | FEPact (kW) | |||
709 | 2600 | 1.37 | 0.76 | 1.30 | 2500 | 1.43 | 0.91 | 1.36 | 2300 | 1.43 | 1.01 | 1.36 | 2100 | 1.50 | 1.04 | 1.42 | 1800 | 1.45 | 1.07 | 1.37 | 1/6 | 1 1/2 |
710 | 3100 | 1.46 | 0.81 | 1.38 | 2800 | 1.41 | 0.96 | 1.34 | 2500 | 1.42 | 1.04 | 1.35 | 2300 | 1.50 | 1.09 | 1.42 | 1900 | 1.48 | 1.07 | 1.40 | 1/6 | 1 1/2 |
712 | 4400 | 1.96 | 0.83 | 1.81 | 4000 | 1.97 | 0.95 | 1.82 | 3600 | 2.00 | 1.04 | 1.85 | 3100 | 1.94 | 1.09 | 1.80 | 2600 | 1.99 | 1.05 | 1.84 | 1/6 | 2 |
715 | 5700 | 2.78 | 0.72 | 2.51 | 5400 | 2.96 | 0.84 | 2.66 | 4700 | 3.00 | 0.88 | 2.70 | 4000 | 2.98 | 0.90 | 2.68 | 3400 | 3.00 | 0.90 | 2.70 | 1/6 | 3 |
718 | 8500 | 4.90 | 0.63 | 4.29 | 8000 | 4.98 | 0.76 | 4.36 | 7400 | 4.98 | 0.86 | 4.36 | 6700 | 4.91 | 0.93 | 4.30 | 5900 | 4.99 | 0.93 | 4.37 | 1/4 | 5 |
CFM values listed are summarized for convenience. For full performance data refer to our Delair program. | ||||||||||||||||||||||
Power rating (BHP) does not include transmission losses. Performance certified is for installation type B: Free inlet, Ducted outlet. Performance ratings do not include the effect of appurtenances (accessories). | ||||||||||||||||||||||
For expanded FEI data click here. | ||||||||||||||||||||||