400 Series FC Exhauster Belt Drive Utility Blowers

  • Universal frame allows for choice of discharge position.
  • Multiple choice for motor mounting location with each discharge position.
  • Motor mounting hardware supplied with models 407 to 418.
  • Optional platform for models 420 to 425.
  • Keywayed shafts
  • Spider bearing brackets for models 407 - 418. Pillow block bearings with T bar support for models 420, 422 & 425.
  • Ball bearings suitable for -65º to + 250º F.
  • Optional back draft dampers, inlet & outlet screens and belt guards.
  • Shafts 420, 422 & 425 models are keywayed for wheels and pulleys (407 to 418 models for pulleys only). 

 

Contact US

TYPICAL MAXIMUM CFM @ SP
MODEL 1/2” SP 1” SP 1 1/2” SP 2" SP 2 1/2" SP Max HP
407 1000 900 800 700 500 1
409 2100 2000 1900 1850 1750 2
410 2600 2400 2300 2150 2050 2
412 3250 3000 2850 2700 2600 2
415 5260 4850 4500 4150 3550 3
418 6700 6300 5950 5550 5200 5
420 9300 8850 8500 8000 7700 7 1/2
422 10300 9750 9200 8600 8000 7 1/2
425 14300 13400 12550 11850 11400 10
Power rating (BHP) does not include transmission losses. Performance certified is for installation
type B: Free inlet, Ducted outlet. Performance ratings do not include the effect of appurtenances
(accessories).

CFM values listed above are summarized for convenience.

Scroll right to see complete table.

360 Viwer